• Calibration and Setup
General
The SET (setpoint) and DB (deadband) adjustments control the
setpoint and hysteresis for each alarm channel. Internal jumpers
control the alarm type and relay coil energisation.
E
quipment requirements
• Two milliamp current sources, e.g., Portacal 1000.
F
lat bladed screwdriver (blade width less than 2.54 mm / 0.1 inch)
Setpoint (SET Control) adjustment
The SET controls for each channel are on the front panel of the
transmitter. For both high and low type alarms you turn the control
clockwise to trip the alarm and anticlockwise to reset it. The procedure
for adjustment is as follows:
1. Connect up the instrument according to the table above.
2. S
et source B to 4 mA.
3. Adjust source A to give the required current difference.
4. Turn the SET control anti-clockwise until the LED extinguishes.
5. S
lowly turn the SET control clockwise until the LED lights up.