Weidmuller DPARES - Universal glavanically isolated signal co Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Matériel Weidmuller DPARES - Universal glavanically isolated signal co. Weidmuller DPARES - Universal glavanically isolated signal converter Benutzerhandbuch Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 24
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
de
en
DPA/RES 61001039/00/04.08
Bedienungsanleitung
Zweikanaliges
Grenzwertüberwachungsmodul 3
Operating instructions
Two-channel
threshold monitoring module 14
Vue de la page 0
1 2 3 4 5 6 ... 23 24

Résumé du contenu

Page 1 - Operating instructions

deenDPA/RES 61001039/00/04.08BedienungsanleitungZweikanaliges Grenzwertüberwachungsmodul 3Operating instructionsTwo-channel threshold monitoring m

Page 2

10Totbandeinstellung (Regler DB)Der Totbandregler dient zum Einstellen des Schaltpunktes, bei dem der ausgelöste Alarm zurückgesetzt werden soll. Bei

Page 3

11• ModifizierungLinke Seitenwand entfernenHinweis: Trennen Sie das Gerät von der Stromversorgung, bevor Sie diesen Vorgang ausführen. 1. Lösen Sie di

Page 4 - Betrieb

125. Lösen Sie die beiden Schrauben an der rechten Seitenwand.(Entsprechend der Schrauben G & H an der linken Seite). Merken Sie sich die Lage des

Page 5

13DPA-Hauptplatine und Darstellung der Steckbrücken für Relaisspulenerregung und AlarmfunktionenBrücken für die Auswahl der Relaisspulenerregung:Kanal

Page 6

14en DPA/RESContentsOperation 15Installation 16Calibration and Setup 19Modifications 21

Page 7

15en DPA/RES• OperationGeneralThe DPA/RES allows you to set two independent trip points against the measurement taken by a resistance based sensor. Th

Page 8 - Anschlüsse

16IndicationThe front panel status LEDs indicate an alarm condition regardless of the coil energisation setting.IsolationInput, Power Supply, Alarm Ch

Page 9

17Alarm connectionsThe DPA has a high inbuilt immunity to noise spikes caused by switching inductive loads like solenoids or relay coils. However, it

Page 10

18Input Signal CablingUse suitable twisted pair cable for the input signal connection.ConnectionsTerminal Signal1 Not UsedInput signals2 Resistance El

Page 11 - • Modifizierung

19• Calibration and SetupGeneralThe SET (setpoint) and DB (deadband) adjustments control the setpoint and hysteresis for each alarm channel. Internal

Page 13

20Deadband (DB Control) adjustmentThe deadband control adjusts the point at which a tripped alarm resets. This point will be above the setpoint for a

Page 14

21• ModificationsRemoving the left hand side plateNote: Remove power from the unit before you attempt this. 1. Remove the six self tapping screws mark

Page 15 - Operation

22DPA main board showing the locations of the high/low operation, andrelay coil energisat ion, selection jumpersRelay energisation selection jumpers:C

Page 17

Weidmüller Interface GmbH & Co. KGPostfach 303032720 DetmoldKlingenbergstraße 1632758 DetmoldTel. +49 5231 14-0Fax +49 5231 14-20 83info@weidmuell

Page 18 - Connections

3de DPA/RESInhaltsverzeichnisBetrieb 4Installation 5Kalibrierung und Konfiguration 9Modifizierung 11

Page 19 - • Calibration and Setup

4de DPA/RES• BetriebAllgemeinDas DPA/RES bietet die Möglichkeit, für eingangsseitige Widerstandsmessungen zwei unabhängige Schaltpunkte festzulegen. D

Page 20

5LED-AnzeigeDie Status-LEDs an der Frontplatte zeigen unabhängig von der Einstellung der Spulenerregung die Alarmzustände an.IsolierungEingangskreis,

Page 21 - • Modifications

6AlarmanschlüsseDas DPA zeichnet sich durch eine hohe Störfestigkeit gegenüber Impulsen aus, die beim Schalten induktiver Lasten wie Solenoid- oder Re

Page 22

7Verwenden Sie eine für Temperaturen von über 70 °C zugelassene Anschlussleitung (12-28 AWG), und schließen Sie diese mit einem Drehmoment von 0,5 Nm

Page 23

8AnschlüsseKlemme Signal1 Nicht belegtEingangssignale2 Widerstandselement3 Nicht belegt4 Widerstandselement5Nicht belegt6789 Neutral (−)Stromversorgun

Page 24

9• Kalibrierung und KonfigurationAllgemeinSollwert und Hysterese der einzelnen Alarmkanäle werden über die Potentiometer SET (Sollwert) und DB (Totband