31
Communications Setup
Allows you to configure the RS422/RS485 outputs.
Display Setup
Sets up display scrolling options.
ENT
EXIT
EXIT
EXIT
ENT
Calibration Mode
Prev Next
To Run
Mode
Calibrate P.I.N
101
Default PIN = 101
Lower PIN
Calibrate Output
Prev Next
ENT
Calibrate Input
Prev Next
Select which input to calibrate
Previous Output Channel
ENT
Ca ibrate Output
Next Output Channel
EXIT
Exit
Calibrate
Output 1
Raise PIN
ENT
Input calibration Procedure (see below)
EXITMENU
ENT
Invalid PIN
Menu->Retry
• Calibration Mode
General
The RI4 is factory calibrated. Once calibrated it will operate with
any input or output format without calibration. Yo
u should not have to
calibrate the unit before installation.
Allow the instrument 15 minutes of powered operation (to reach a
stable temperature) before calibration.
During calibration allow a few seconds for signals to stabilise before
accepting the value.
Equipment requirements
• A suitable Pt100 RTD Simulator (must be able to simulate Pt100 to
±0.05 % or better accuracy)
• An accurate digital multimeter (accurate to 0.05 mV and ±0.1 μA)