27
EMC specification according to EN 55011, class B,
group 1
according to EN 50081-1
according to EN 50082-2
General
Current consumption
- by current output 28 mA ... 33 mA ... 38 mA
I
out
= 20 mA
- by voltage output 18 mA ... 23 mA ... 28 mA
U
out
= 10 V
Voltage supply 19.2 Vdc ... 24 Vdc ... 28.8 Vdc
Cross-connection, upper 24 V, max. 2 A
Cross-connection, lower 0 V, max. 2 A
Operating temperature 0 ... +55 °C
Storage temperature -20 ... +85 °C
Approvals CE, CSA, UL